'Horizontal' flue outlet pipework MUST slope at least 2.5
degrees (45 mm per metre run) downwards towards the
boiler. Pipework can be vertical. Only swept elbows can be
used. For installations requiring reduced slope contact
Keston Boilers Technical Support.
Air inlet pipework can be truly horizontal or vertical, or
sloping in a downward direction towards the boiler but in
this case rain, etc, must be prevented from entering the
pipe. There must be no troughs in any of the pipework,
whether it be air inlet or flue outlet.
Due to the low temperature of the flue
gases further condensate will form within
the flue system. Drain points, with
suitable traps, must therefore be
incorporated within the flue
system at the base of vertical flue sections
in excess of 4m (2m for the Keston 130
and Keston 170). These additional
condensate drains must be run to discharge as detailed in
section "Condensate Drainage". Such drain points can be
formed using standard Keston Composite flue fittings.
Terminations
Air inlet terminals must be positioned to ensure only fresh
air is drawn into the boiler. The air terminal must be located
outside of the building.
Drawing of combustion air directly from a ventilated boiler
room will invalidate the heat exchanger warranty.
The flue outlet terminal is designed to face outwards but
can, if desired, be adapted to face in any direction BUT must
not be directed in the region of the air inlet. Where the air
and flue terminals are located in close proximity the flue
terminal should be located above the level of the air inlet
terminal.
The two terminals are subject to the requirements of BS
5440 Pt 1 for clearances from features of the building
although some can be decreased to the values indicated.
If either the air inlet or the flue outlet terminate at a height
of less than 2m (6ft) above ground level the termination
must be protected by a suitable guard. Suitable terminal
guards can be obtained from Tower Flue Components Ltd
or its distributors.
The Keston Condensing Boiler, as with any condensing
boiler, will generate a condensate "plume" from the flue
terminal in all weather conditions. Consideration must
therefore be given to the effect of this "plume" when
selecting a location for the flue terminal.
It is advisable for horizontal flue terminals to place a 45°
elbow at the end of the flue to direct the condensate plume
up and away from the property.
Flue outlet and air inlet terminations must be at least 60 mm
and 95 mm respectively from the wall face.
There is no maximum distance between flue terminal and
air inlet terminal - the terminations can be on opposite sides
of the dwelling if desired.
A minimum clearance of at least 500 mm must be left
between the terminations.
Compartment Installation
The casing temperatures of the Keston commercial boilers
are very low. Due to this fact, no compartment ventilation is
required for cooling purposes.
Condensate Drainage
Being a condensing boiler, the Keston is fitted with a
condensate trap at the base of the heat exchanger and flue
assembly, with facility to connect to a drain point underneath
the appliance.
Use only plastic piping and do not reduce below 22mm
internal diameter within the dwelling. Condensate should
preferably be drained into the sanitary waste system or,
alternatively, the rainwater system of the property.
Termination of the pipe must be either at a branch or stack
internal to the building, or externally at an open gully.
Alternatively, discharge into a purpose made condensate
soakaway can be considered. Existing or purpose built drains
must use suitable corrosion resistant material as condensate
is mildly acidic.
A minimum slope downwards towards the drain of 1 in 20
is essential. Freezing of the termination and pipework must
be prevented. Any drainage pipes outside the property must
be at least 32 mm inside diameter.
To Terminal
To Boiler
Te e
Fitting
6 in
min
6
Minimum Flue Terminations and Flue Air
Air Inlet Dimensions (mm) Terminal Inlet
A Below or beside openable window, air brick etc. 500 50
B Below gutters, soil pipes, drain pipes 75 75
C Below eaves 300 50
D Below balconies or car port roof 200 50
E From vertical drain or soil pipes 75 50
F From internal or external corner 600 50
G Above ground or balcony or roof 300 100
H From surface facing a terminal 600 100
I From terminal facing a terminal 1200 1200
J From opening in a car port 1200 100
K Vertically from terminal on same wall 1500 1500
L Horizontally from terminal on same wall 300 300
Page view 5