C45 C40P C55 C55P
Fan Powered High Efficiency
Modulating Domestic Condensing Gas Boiler
Installation and Servicing Instructions
C45, C40P, C55 & C55P Models
ISSUE: 1/2010
CE/PI No : 87CL131
C45 - GC No : 41-930-25
CE/PI No : 87BN14
C40P - GC No : 41-930-08
C55 - GC No : 41-930-09
C55P - GC No : 41-930-10
These instructions must be left either with
the user or next to the site gas meter.
KESTON BOILERS LIMITED
34 West Common Road, Bromley, Hayes, Kent BR2 7BX, UK
Tel. +44 (0)20 8462 0262 Fax. +44 (0)20 8462 4459
email : [email protected]o.uk web : www.keston.co.uk
COMPLIANT WITH BUILDING REGULATION PART L1 & L2 2002
SEDBUK A RATED
WD536 The Keston C45, C40P, C55 & C55P
Page view 0
1 2 3 4 5 6 ... 53 54

Summary of Contents

Page 1 - C45 C40P C55 C55P

C45 C40P C55 C55PFan Powered High Efficiency Modulating Domestic Condensing Gas BoilerInstallation and Servicing InstructionsC45, C40P, C55 & C

Page 2 - CONTENTS

Keston Boilers Ltd declare that there are no substances harmful to health within theappliance or used during the production of the applia

Page 3

1.7 OPTIONAL ACCESSORIESA range of accessories are available from Keston Boilers Ltd to compliment an installation.Terminal wall sealing

Page 4 - Page : iii

2. BOILER LOCATION2.1 DIMENSIONS AND MINIMUMCLEARANCESThe boiler must be installed in minimumclearances shown to allow subsequentservicing, and s

Page 5 - Page : iv

cannot be touched by a person using the bath or shower. The C45, C40P and C55(P) areclassified as IP20 (IPX0) and are therefore suitable for installat

Page 6 - 1. GENERAL INSTRUCTION

BS 1363. There must be only one common method of isolation for the boiler andits control system.The appliance must be connected to the 3A supply via a

Page 7

Gas pressures above or below these levels will lead to problems associated with the gasvalve's internal pressure regulator.Supply pipes to the bo

Page 8

valves are closed, then the safety valve may be omitted. Note that the minimumstatic head required is 9 ft at the top of the boiler. Although suitabl

Page 9 - (Factory Preset)

All components of the system including the heat exchanger of the indirect cylindermust be suitable for a working pressure of 3 bar and a temperature o

Page 10

2.7.3 Hot Water System (if applicable)The hot water storage vessel must be of the indirect type (certain direct cylinderscan be used provided they are

Page 11

Installation of air bleed valves at the high spot(s) in the system will allow for airelimination when filling the system and will allow re-venting in

Page 12 - 2. BOILER LOCATION

CONTENTSSection Description0 HANDLING INSTRUCTIONS0.1 List of contents0.2 Recommended handling procedure1 GENERAL INSTRUCTION1.1 Description1.2 Boiler

Page 13

Alternatively, where flue or air intakelengths of up to 45m are require,Glynwed Friatec DN70 pipe may beused. Both 50mm flue outlet terminal and

Page 14

2.8.3 Boiler Output vs Flue LengthDue to the resistance presented by extended flue length a slight reduction inmaximum boiler output wi

Page 15

300300L Horizontally from terminal on same wall.1,5001,500K Vertically from terminal on same wall.1001,200J From opening in a car port.1,2001,200I Fro

Page 16 - (See note 2.7.1)

2.11 CONDENSATE DRAINAGEBeing a condensing boiler, the C45, C40P and C55(P) are fitted with a condensate trap atthe base of the heat exchanger and flu

Page 17

3. INSTALLATION OF THE BOILERRead Chapter 2 - Boiler Location and decide upon the position of the boiler.Installation of the boiler is straightforward

Page 18

Remember the flue pipe must slope downwards back towards the boiler and thisis best achieved using 92.5o bends.a Using the template supplied within th

Page 19

3.6 WATER SYSTEMConnect the flow and return pipework to the boiler. Details of system requirements aregiven in Chapter 2 - Section 2.7 Water Systems

Page 20 - C45 or C55

3.9 EXCHANGING A BOILERBefore removing an existing boiler add Fernox Supafloc , or equivalent cleaning agent, inaccordance with the manufacturers’

Page 21 - 6 in min

4. COMMISSIONING OF THE BOILERImportant:This condensing boiler contains components which could be damaged or blocked by grease, dirt,solder etc., fr

Page 22

e. Adjust the upper rotary control knob, central heating temperature, to themaximum clockwise position. Adjust the lower rotary control know, DHWtempe

Page 23

4 COMMISSIONING OF THE BOILER4.1 Initial Flushing4.2 Gas Supply4.3 Electrical Installation4.4 LP Gas 4.5 Initial Firing4.6 Hot Flushing4.7 Combustion

Page 24 - 3. INSTALLATION OF THE BOILER

To measure CO2 levels in the Keston boiler remove the 1/8" plug from the flue outlet pipespigot (Figure 5.7.4 item 18). Insert the probe of a cal

Page 25

LESS THAN THE CO2 LEVEL AT HIGH RATE. ADJUSTMENTS, IF MADE, SHOULD BEIN STEPS OF NO MORE THAN 1/8 OF A TURN. YOU MUST WAIT 1 MINUTE AFTEREACH ADJUSTME

Page 26

4.10 HANDING OVER TO THE USERIt is important to fully explain the following:a. Procedure to light and turn off the boiler, including isolation of the

Page 27

5. FAULT FINDING5.1 ELECTRICAL CONTROL SEQUENCEWhen the external controls are calling for heat, power will be fed to the boiler connectionstrip at te

Page 28

QUICK REFERENCE5.2 NORMAL OPERATIONThe C45, C40P and C55(P) boilers feature a user display which shows actual flow temperature atall times (the last t

Page 29

5.3.2 LOCKOUT If the fault is persistent or more severe the boiler will lockout with a error code. When the boilerhas entered this error mode it will

Page 30

5.4 FUNCTIONAL FLOW WIRING DIAGRAMWD536 Chapter 5 : Fault Finding The Keston C45, C40P, C55 & C55PInstallation & Servicing Instructions Page

Page 31

5.5 ELECTRICAL WIRING DIAGRAMWD536 Chapter 5 : Fault Finding The Keston C45, C40P, C55 & C55PInstallation & Servicing Instructions Page :

Page 32

5.6 ILLUSTRATED WIRING DIAGRAMWD536 Chapter 5 : Fault Finding The Keston C45, C40P, C55 & C55PInstallation & Servicing Instructions Page :

Page 33 - 5. FAULT FINDING

5.7 Exploded Assembly Diagrams5.7.1 Boiler Controls Assembly WD536 Chapter 5 : Fault Finding The Keston C45, C40P, C55 & C55PInstallation & S

Page 34 - QUICK REFERENCE

0. HANDLING INSTRUCTION0.1 LIST OF CONTENTSThe Keston C40P,C45 and C55(P) are supplied almost totally pre-assembled. Since the unitsuse standard 50 mm

Page 35 - 5.3.2 LOCKOUT

5.7.2 Waterway, Condensate & Flue AssemblyWD536 Chapter 5 : Fault Finding The Keston C45, C40P, C55 & C55PInstallation & Servicing Instru

Page 36

5.7.3 Air - Gas AssemblyWD536 Chapter 5 : Fault Finding The Keston C45, C40P, C55 & C55PInstallation & Servicing Instructions Page : 36

Page 37 - 5.5 ELECTRICAL WIRING DIAGRAM

5.7.4 Casing AssemblyWD536 Chapter 5 : Fault Finding The Keston C45, C40P, C55 & C55PInstallation & Servicing Instructions Page : 37

Page 38

5.7.5 Exploded Diagrams Parts Reference ListBoiler Controls Assembly (Fig. 5.7.1)GC Number Code DescriptionE93-126 88 C55/C55P/C45 Main Control Box (

Page 39

6. ROUTINE (ANNUAL) SERVICINGTo ensure the continued safe and efficient operation of the boiler it is necessary to carry outroutine se

Page 40

b. Remove the burner head (Section 7.6) and inspect the burner appearance. Blackmarkings or other discoloration's on the gauze indicate too much

Page 41 - 5.7.3 Air - Gas Assembly

7. REPLACEMENT OF PARTSCONTENTS7.0 GENERAL7.1 PRECAUTIONS7.2 ACCESS7.3 REPLACEMENT PROCEDURE7.4 ELECTRICAL COMPONENTS7.4.1 CONTROL PANEL7.4.2 BOILER F

Page 42 - 5.7.4 Casing Assembly

7.4.2 Boiler Flow and Return Thermistors (Fig. 5.7.2 item 47)i) Isolate the appliance (Section 7.1)ii) Gain access (Section 7.2)iii) Remove the push o

Page 43

7.4.8 Gas Control Valve / Venturi Assembly (Fig. 5.7.3 item 163)i) Isolate the appliance (Section 7.1)ii) Gain access (Section 7.2)iii) Remove the pus

Page 44

xi) Remove the two screws fixing the heat exchanger to the top mounting bracket(Fig 5.7.2 item 63)xii) Remove the heat exchangerxiii) Reassemble (Sect

Page 45

In the event the appliance must be fitted by one operative the integral circulating pump headand complete combustion fan/gas valve/venturi assembly ca

Page 46 - 7. REPLACEMENT OF PARTS

8. SHORT SPARE PARTS LISTItem GC No Part Denomination Item GC No PartDenomination77 E93-137 C55 Burner 44 E93-141 Burner GasketE93-138 C55P/C45/C40P

Page 47

SHORT SPARE PARTS LIST FOR THE KESTONCONDENSING BOILER RANGEItem GC No Part Denomination47 E93-145 Flow/Return Temperature Thermistor48 114-045 Water

Page 48

WD536 Chapter 9 : Benchmark Checklist Final The Keston C45, C40P, C55 & C55P Installation & Servicing Instruction

Page 49

WD536 Chapter 9 : Benchmark Checklist Final The Keston C45, C40P, C55 & C55P Installation & Servicing Instruction

Page 50

†Read Installation Manual Carefully†Ensure that there is at least 9 feet head of water pressure at thetop of the boiler .†Ensure that ALL dust p

Page 51 - CONDENSING BOILER RANGE

1. GENERAL INSTRUCTION1.1 DESCRIPTIONThe Keston C45, C40P and C55(P) are unique in concept and design. They comprise ahigh efficiency stainless ste

Page 52 -

the flueway and is drained at the base of the flue connection to the heat exchanger ordrain points within the flue.Fig. 1.2 - Boiler LayoutThe conde

Page 53 - SERVICE INTERVAL RECORD

In addition, due account must be taken to the following Codes Of Practice:BS 6891 : Low Pressure Installation PipesBS 6798 : Installation of Gas Fired

Page 54 - C45, C40P & C55(P)

1.5 PERFORMANCE DATA - C45 & C40P1.6 PERFORMANCE DATA - C55 & C55PWD536 Chapter 1 : General Instruction The Keston C45, C40P, C55 and C55PIn