INSTALLATION
Keston Combi - Installation and Servicing
FLUE OUTLET
12
FLUE TERMINATION POSITION
Twin Flue Positions
Below an opening (1)
Above an opening (1)
Horizontally to an opening (1)
Below gutters, soil pipes or drain pipes
Below eves
Below balcony or car port roof
From a vertical drain pipe or soil pipe
From an internal or external corner or to a boundary alongside the terminal
Above ground, roof or balcony level
From a surface or a boundary facing the terminal
From a terminal facing the terminal
From an opening in the car port into the building
Vertically from a terminal on the same wall
Horizontally from a terminal on the same wall
300 mm
300 mm
300 mm
75 mm
200 mm
200 mm
150 mm
300 mm
300 mm
600 mm
1200 mm
1200 mm
1500 mm
300 mm
50 mm
50 mm
50 mm
75 mm
50 mm
50 mm
50 mm
50 mm
100 mm
100 mm
1200 mm
100 mm
1500 mm
300 mm
2"
2"
2"
3"
2"
2"
2"
2"
4"
4"
48"
4"
60"
12"
12"
12"
12"
3"
8"
8"
6"
12"
12"
24"
48"
48"
60"
12"
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
Flue Minimum Spacing Air Minimum Spacing
(1) An opening here means an openable element, such as a openable window, or a fixed opening such as an air vent. However, in addition, the outlet should not
be nearer than 150mm (fanned draught) to an opening into the building fabric formed for the purpose of accommodating
a built in element, such as a window frame.
The dimensions given in the table above may need to be increased to avoid wall staining and nuisance depending on site conditions.
boundary
boundary
J
H
L
F
I
G
I
A
B
C
D, E
H
H
K
M
N
GENERAL INSTALLATIONS
All parts of the system must be constructed in accordance with BS 5440 Part 1, except where specically mentioned in these
instructions.
All pipe work must be adequately supported.
All joints other than approved push-on or plastic compression connectors must be made and sealed with solvent cement suitable
for muPVC pipes and conforming to BS 6209: 1982.
Consideration must be given to Corgi/Gas Safe bulletin TB200/TB008 regarding ues in voids.
The boiler casing must always be correctly tted to the boiler when leaving the appliance operational.
External wall faces and any internal faces of cavity walls must be good.
AIR SUPPLY
The Keston Combi is a room-sealed appliance and therefore does not require purpose provided ventilation to the boiler room for
combustion air.
COMPARTMENT INSTALLATION
Due to the low casing temperatures generated by the boiler, no compartment ventilation is required. However, the cupboard or
compartment must not be used for storage.