11Keston Combi - Installation and Servicing
general
The boiler does not normally need a bypass but at least
some radiators on the heating circuit, of load of at least
10% of the minimum boiler output, must be provided with
twin lockshield valves so that this minimum heating load
is always available. See note regarding thermostatic
radiator valves on page 8.
Note. Systems incorporating zone valves which could
completely cut off the ow through the system must also
include a bypass.
BALANCING
1. Set the programmer to ON.
Close the manual or thermostatic valves on all
radiators, leaving the twin lockshield valves (on the
radiators referred to above) in the OPEN position.
Turn up the room thermostat and adjust the
lockshield valve to give an uninterrupted ow through
the radiator.
These valves should now be left as set.
2. Open all manual or thermostatic radiator valves
and adjust the lockshield valves on the remaining
radiators, to give around 20
o
C temperature drop at
each radiator.
3. Adjust the room thermostat and programmer to
NORMAL settings.
4
SYSTEM BALANCING
3
SYSTEM REQUIREMENTS cont’d
DOMESTIC HOT WATER
1. The domestic hot water service must be in accordance with
BS 5546 and BS 6700.
2. Refer to Table 1 for minimum and maximum working
pressures. In areas of low mains water pressures the
domestic hot water regulator may be removed from the DHW
ow turbine cartridge. Refer to Frame 70. The boiler will
require the ow rate to be set to obtain a temperature rise of
35
o
C at the tap furthest from the boiler.
3. The boiler is suitable for connection to most types of washing
machine and dishwasher appliances.
4. When connecting to suitable showers, ensure that:
a. The cold inlet to the boiler is tted with an approved anti-
vacuum or syphon non-return valve.
b.
Hot and cold water supplies to the shower are of equal
pressure.
5. Hard Water Areas
Where the water hardness exceeds 200mg/litre, it is
recommended that a proprietary scale reducing device is
tted into the boiler cold supply within the requirements of the
local water company.
IMPORTANT
Provision MUST be made to accommodate the expansion of DHW
contained within the appliance, if a non-return valve is tted to the
DHW inlet, or a water meter with a non-return valve is installed.
Cold water rising main and pipework in exposed areas need to
be suitably lagged to prevent freezing.
5
WATER TREATMENT
CENTRAL HEATING
The Keston Combi range boiler has an ALUMINIUM alloy
heat exchanger.
IMPORTANT.
The application of any other treatment to this product
may render the guarantee of Keston Invalid.
Keston recommend Water Treatment in accordance with the
Benchmark Guidance Notes on Water Treatment in Central
Heating Systems.
If water treatment is used Keston recommend only the use
of SCALEMASTER GOLD 100, FERNOX, MBI, ADEY MC1 or
SENTINEL X100
inhibitors and associated water treatment
products, which must be used in accordance with the
manufacturers’ instructions.
Notes.
1. It is most important that the correct concentration of the
water treatment products is maintained in accordance
with the manufacturers’ instructions.
2. If the boiler is installed in an existing system any
unsuitable additives MUST be removed by thorough
cleansing. BS 7593:2006 details the steps necessary to
clean a domestic heating system.
3. In hard water areas, treatment to prevent lime scale may
be necessary - however the use of articially softened
water is NOT permitted.
4. Under no circumstances should the boiler be red
before the system has been thoroughly ushed.
DOMESTIC HOT WATER
In hard water areas where mains water can exceed 200ppm
Total Hardness (as dened by BS 7593:2006 Table 2) a scale
reducing device should be tted into the boiler cold supply within
the requirements of the local water company. The use of articially
softened water, however, is not permitted.
Keston recommend the use of Fernox Quantomat, Sentinel
Combiguard or Calmag CalPhos I scale reducing devices together
with scalemaster in-line scale inhibitor branded Ideal, which must
be used in accordance with the manufacturers’ instructions.
For further information contact:
Fernox Cookson Electronics
Forsyth Road, Sheerwater, Woking, Surrey GU21 5RZ
+44 (0) 870 601 500
Sentinel Performance Solutions
The Heath Business & Technical Park, Runcorn, Cheshire WA7 4QX
Tel: 0800 389 4670
www.sentinel-solutions.net
Scalemaster Water Treatment Products
Emerald Way, Stone, Staffordshire ST15 0SR
Tel: +44 (0) 1785 811636
Calmag Ltd.
Unit 3-6, Crown Works, Bradford Road, Sandbeds, Keighley,
West Yorkshire BD20 5LN
Tel: +44 (0) 1535 210 320
Adey Professional Heating Solutions
Gloucester Road, Cheltenham GL51 8NR
Tel: +44 (0) 1242 546700
Page view 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 71 72

Comments to this Manuals

No comments